Arizona State University College of Liberal Arts and Sciences
Home | About the Lab| The Analytical Side | The Science   

 

Infrastructure - Keck Lab Air Supply

The air supplied to the lab-space is conditioned by multiple steps between the air intake and the supply ducts in the room. Here is a general description of how the air is treated and how it can be monitored.

 

I] Conditioning steps:

Location Conditioning steps Monitored status
1) Air intake 100% Outside air is drawn into the air handler (there is no air recycling for the Keck Lab) Outside air temperature

Outside air humidity

2) Air handler intake Air is filtered through prefilters and HEPA filters Magnehelic gauge on air handler indicates how clogged filters are. New filters should read <0.5 inch pressure drop. When drop is 1.0 inches then it is time to replace the prefilters. HLPA filters are replaced once every 6 months.

VFD 1 and 2 Speed (there is one variable frequency drive (VFD) that runs the air handler fans and a second one that serves as a backup should the first one fail. Their status can be monitored. At all times one of them should indicate that it is not active.)

3) Air handler a) Air is cooled to the cooling coil temperature in order to remove excess moisture. The setpoint for this is usually 46°f in the monsoon season, and 53°f in the dry season. Note that too low a cooling point can result in insufficient humidification of the instrument lab. Cooling Coil Setpoint

Cooling Coil Temperature

b) Air is heated to the setpoint for the air handler discharge. (55°f) Discharge Air Temperature

Cooling Setpoint

Cooling-heating-setpoint

Cooling Output (monitors how much the cooling valve is open)

Heating Output (monitors how much the heating valve is open)

c) Air is humidified to set level (70%) Discharge Air Humidity

Discharge Air Humidity Setpoint

d) Air handler fan speed is adjusted to maintain the static pressure setpoint in the main duct in the corridor. (current setpoint is 2.00 inches of water) Supply Fan Output (gives fan speed in %. Note that 100% corresponds to 90 Hz)

Discharge Air Static Pressure

Discharge Air Static Setpoint (this value has changed over the life of the lab when we had air handler problems. Value as of May 2007 is 2.00 in wc)

4) Corridors Chilled air runs to the various lab supply ducts. Herckes Lab (PSF-7) as well as the Keck Lab (minus metallomics and the conference room) are supplied by this air. The status of this air can only be monitored by the main duct pressure (Discharge Air Static Pressure) and the discharge air temperature and humidity monitored at the air handler.
Air is split through the different Phoenix Valves to the different lab spaces. NOTE THAT ALL AIR SUPPLY PHOENIX VALVES ARE MANUALLY CONTROLLED ONLY. NONE OF THEM ARE MONITORED ELECTRONICALLY. Pressure drops across the phoenix valves can be measured with the department meter.
5) Lab space above ceilings Air is heated to maintain the room temperature setpoint Monitor the Reheats on the metasys server. Reheats indicate local discharge air temperature as well as how open the heating coil is.
6) Air supply ducts Air passes through HEPA filters to the instrument lab areas, and through ULPA filters to the clean lab space. There is no additional filtration for the general lab. Pressure drops across the filters can be monitored to determine the status of the filter. A clogged filter will have a drop of > 1 in wc.
7) Exhaust ducts a) Air passes through exhaust grids or ducts in the various rooms. a) Dampers: many of the ducts have dampers which offer coarse control of the air flow out of a room (or instrument).

b) Phoenix valves: some systems have manually controlled Phoenix Valves to obtain a fixed room exhaust.

c) Phoenix valves: several rooms have electronically monitored and controlled Phoenix Valves which can be reset by Building Automations on campus (Call FACMAN at 5-3633 and ask to be put through to building automations). These all provide a fixed exhaust flow and may have several ducts leading to them. For example, exhaust valve 29 (in room F-10) controls the exhaust for a Neptune, future Element-2, several standalone hoods, the X-series ICP, and the gIRMS exhausts. Closing the damper for one of these items will result in an increased exhaust in the other ducts so as to maintain the same total exhaust through the valve.

8) Instrument lab prep room (PSF-10C) The exhaust air from half of the clean lab and the Herckes lab joins up with exhaust air from the clean lab, general lab, metallomics, and the instrument lab right above the ceiling in this room. It used to be an elevator shaft.  
9) Building roof There are two main exhaust fans on the building roof top. They are set to a constant speed by Building Automations. They do not automatically change speed to maintain a constant static pressure in the main exhaust rise in the elevator shaft. Exhaust static pressure

Exhaust fan (1 and 2) speed

Go to the top of the building and have a look at these huge fans with Chris. Note that there are dampers on these exhaust fans and they have occasionally closed partially or failed during the hot summer months (mainly the ones on the east fan). If there are exhaust issues in the lab in the summer, this is a place to look.

 

II] Monitoring the laboratory climate control system:

It is possible to monitor the lab status from a PC on or off campus, however, one will first need to gain access to the metasys server which is done via the lab manager. Once on the metasys server, here is what you will see:

 

 

Double click on the first "AHU-1" heading and here is what you will see:

In the image above, the "value" is either a setpoint or a readback. These numbers update every 30 seconds or so. What's more important to see here is the description given on the left. We frequently prefer to look at trends over the last week or longer. To do so, it is necessary to open the appropriate folder on the left and then find the correct item. For example, if we would like to see the instrument lab room temperature over the last week, then we'll need to find the appropriate tab for it.

In the screen shot above, the current readback values and their description are listed on the right. However, to access the trending data we need to doubleclick on the appropriate tab in the left window. For the room temperature it will be the file ending in ZN-T (short for zone temperature). Double clicking on that gives the following screen:

To access the weekly trend data, click on the "trend" tab. Here is the result:

If you click on the chart box (just under the "delete" button on the screenshot above) then you can access a table of values for the temperature. Highlight the top line and press CNTRL-A to highlight all of the content of the table. Now click on the "copy to clipboard" button and you can paste all of this into notepad and transfer it to excel.

 

There are many, many parameters of the laboratory climate control system that are accessible on the metasys server. The only way to find out about them is really to play with it for some time and try to understand what each item is. After looking through the system for some time, the parameter names will start to make some sense.

 

 

Page last updated: May 20, 2007

Contact us :

Address: Physical Sciences F-686 Box 1404 Arizona State University Tempe, AZ 85287-1404
Tel: 480-727-8033 Fax: 480-965-8102 E-mail: kfleb@asu.edu

Technical Problems | Privacy | Copyright | Accessibility